Eaton 93PM 480V UPS
HK$0.00
Eaton Energy Saver System (ESS)
The 93PM’s ESS energy cost savings can pay for the UPS in less than three years.
Ease of management
● Provides easier access to detailed status information
● Optimizes server virtualization through power management and connectivity software
● Increases uptime with 24x7 remote monitoring and reporting capabilities
Eaton lithium-ion battery systems
Compatible with the 93PM UPS and 9395 UPS family, lithium-ion battery systems offer a compact, lightweight solution with significant TCO savings for your environment.
Bundle up with PredictPulse
PredictPulse is now included at no extra charge for one year with all 93PM UPS models purchased after January 2022. Eaton service technicians will install and activate this service during startup using a cellular broadband modem/router, making the setup process seamless.
Warranty and service plans
Eaton's UPS warranty and service options provide the system uptime, convenience and value that is right for you and your business.
Eaton 93PM 480V UPS technical specifications
| Power modules for 250 kW frame | |
| Power offering (kW) | 50, 100, 150, 200, 250 kW with optional internal N+1 redundancy through 200 kW |
| General characteristics | |
| Efficiency in Energy Saver System (ESS) mode | Up to 99% |
| Efficiency in double-conversion mode | Up to 97% |
| Height x depth x width | 74" x 42" x 22" |
| Input characteristics | |
| Voltage | 380/400/415V 3-phase (4-wire) 480V 3-phase (3-wire or 4-wire) |
| Voltage range | +10%/-15% |
| Frequency | 50/60 Hz |
| Power factor | > .99 |
| Input current distortion | ≤ 3% @ 100% load capacity |
| Battery | |
| Battery voltage | 432V, 480V (480V required for 480V 4-wire UPS) |
| Charging method | ABM or float technology |
| Output | |
| Voltage | 380/400/415V 3-phase (4-wire) 480V 3-phase (3-wire or 4-wire) |
| Frequency | 50/60 Hz |
| Regulation | ±1% steady state |
| Voltage THD | <1% (100% linear load); <5% (non-linear load) |
| Load power factor range | Unity with the ability to support 0.8 leading to 0.8 lagging without de-rating |
| Certification | |
| Safety | UL 1778, cULus |
| EMC | FCC Part 15 subpart B class A |
| Surge | IEC 61000-4-5 |
| Optional accesories | |
| |